Ethylene oxide (EtO) is a sterilant gas used where heat or steam would damage the product, such as medical devices. California regulates it under 8 CCR §5220, Ethylene Oxide. The standard itself singles out several short sterilization tasks. This post walks through §5220 in the order the standard is written, using its own terms.
Scope, Exemptions and the Limits in §5220(c)
Section 5220(a) covers occupational exposure to EtO. An employer may be exempt for a product where objective data show the product is not capable of releasing airborne EtO at or above the action level under the conditions of processing, use or handling that would reasonably be expected to cause the greatest possible release. That exemption has to be documented, and §5220(k)(1)(C) requires the objective data to be kept for as long as the employer relies on them. Sections 5221 and 5222 also apply to walk-in fumigation or sterilization chambers.
The limits are short:
- Permissible exposure limit, §5220(c)(1): 1 ppm as an 8-hour time-weighted average (TWA).
- Short-term limit, §5220(c)(2): 5 ppm averaged over a 15-minute sampling period. Section 5220 calls this the STEL (short-term exposure limit). The phrase “excursion limit” also appears once, in the labeling provision at §5220(j)(2)(B), but the number set in (c)(2) is the STEL.
- Action level, §5220(b): 0.5 ppm as an 8-hour TWA.
Monitoring frequency, medical surveillance, training and labeling all key off the action level.
Exposure Monitoring Under §5220(d)
Section 5220(d)(1) requires breathing-zone samples representative of each employee’s 8-hour TWA, with full-shift samples taken for each shift, job classification and work area. Initial monitoring under (d)(2) applies to covered workplaces unless the employer is exempt under (a)(2) or has qualifying earlier data. After that, (d)(3) sets the periodic schedule:
- At or above the action level but at or below the TWA: at least every 6 months, (d)(3)(A).
- Above the TWA: at least every 3 months, (d)(3)(B).
- Above the STEL: at least every 3 months and more often as necessary, (d)(3)(D).
- An employer on quarterly monitoring may drop to semiannual when two consecutive measurements taken at least 7 days apart are at or below the TWA, (d)(3)(C).
Monitoring may stop for represented employees when initial monitoring shows exposure below the action level, or when periodic results show two consecutive measurements at least 7 days apart below the action level, under (d)(4)(A) and (B). Section 5220(d)(5) requires additional monitoring whenever a change in production, process, control equipment, personnel or work practices may result in new or additional exposure, or when the employer has reason to suspect such a change.
Under (d)(6), methods must be accurate at 95% confidence to plus or minus 25% at the TWA and 35% at the action level and STEL. Under (d)(7), affected employees must be notified of results in writing, individually or by posting, within 15 working days after the employer receives them, and where the TWA or STEL is exceeded the notice must describe the corrective action being taken.
In the EtO programs I review, I check short-term sampling first. Full-shift averages at a sterilizer can look acceptable while a door opening, a cylinder change or aeration-room entry produces a 15-minute peak above 5 ppm.
Regulated Areas and Methods of Compliance
Under §5220(e), a regulated area must be established wherever exposure may exceed the TWA or can reasonably be expected to exceed the STEL. Access is limited to authorized persons, and the area is demarcated and posted with the §5220(j)(2)(A) signs.
Section 5220(f) requires engineering controls and work practices to reduce exposure to or below the TWA and STEL where feasible, with respirators as a supplement where controls alone are not enough. A note following (f)(1)(B) lists operations where engineering controls are generally infeasible: collecting quality assurance samples from sterilized materials, removing biological indicators from sterilized materials, loading and unloading tank cars, changing EtO tanks on sterilizers, and vessel cleaning.
Where the TWA is exceeded, §5220(f)(2) requires a written compliance program that includes a schedule for periodic leak detection surveys and a written emergency plan. The program must be reviewed and updated at least every 12 months, (f)(2)(C), and (f)(2)(D) prohibits rotating employees to achieve compliance with the TWA or STEL.
Respirators and Protective Clothing Under §5220(g)
Section 5220(g)(1) requires respirators during the time needed to install or implement feasible controls, in work operations such as maintenance, repair and vessel cleaning where controls are not feasible, where feasible controls do not reduce exposure enough, and in emergencies. Under §5220(g)(2), respirators must be used within a respiratory protection program meeting Section 5144(b).
Selection has EtO-specific restrictions:
- Half masks of any type are prohibited because of the potential for eye irritation, (g)(3)(A).
- Air-purifying full facepiece respirators must have a front- or back-mounted canister approved for EtO, (g)(3)(B).
- Any respirator permitted under the standard may be provided for escape, (g)(3)(C).
Where eye or skin contact with liquid EtO or EtO solutions may occur, §5220(g)(4) requires appropriate protective clothing or equipment at no cost to the employee, in line with Sections 3380, 3382, 3383 and 3384.
Emergencies Under §5220(h)
An “emergency” under §5220(b) is any occurrence, such as equipment failure, rupture of containers or failure of control equipment, that is likely to or does result in an unexpected significant release of EtO. Section 5220(h)(1) requires a written emergency plan wherever an emergency is possible. The plan must provide for respiratory protection for employees engaged in correcting the emergency and must include the elements of Sections 3220 and 3221.
Under §5220(h)(2), the employer must provide a means of promptly alerting potentially affected employees. Employees not engaged in correcting the emergency must be evacuated immediately and kept out until the emergency is abated. Section 5220(h)(3) requires emergencies to be reported to the Chief as provided in the standard’s notification subsection.
Medical Surveillance Under §5220(i)
Section 5220(i)(1)(A) requires a medical surveillance program for employees who are or may be exposed at or above the action level for at least 30 days a year, without regard to respirator use. The standard uses the term “physician,” and (i)(1)(C) requires that examinations be performed by or under the supervision of a licensed physician and provided without cost to the employee and without loss of pay.
Under §5220(i)(2), examinations are made available before assignment to an area where exposure may be at or above the action level for at least 30 days a year; annually for employees so exposed during the preceding year; at termination of employment or reassignment out of such an area; as medically appropriate after exposure in an emergency; as soon as possible after an employee reports signs or symptoms or requests advice on reproductive effects; and more often if the physician recommends. The content is listed in (i)(3)(A): a medical and work history, a physical examination, a complete blood count including differential, red cell count, hematocrit and hemoglobin, and any other tests the physician deems necessary.
The physician’s written opinion under §5220(i)(5) addresses conditions that would place the employee at increased risk, any recommended limitations, and a statement that the employee was informed of the results. Findings unrelated to occupational exposure may not be revealed to the employer, and the employer must give the employee a copy of the opinion within 15 days of receiving it, (i)(5)(C). Medical records are kept for employment plus 30 years, §5220(k)(3)(C); exposure records for at least 30 years, (k)(2)(C).
Signs, Labels and Training Under §5220(j)
Section 5220(j)(1) ties hazard communication to Section 5194. The regulated-area sign in (j)(2)(A)1 begins “DANGER / ETHYLENE OXIDE / MAY CAUSE CANCER” and continues with “MAY DAMAGE FERTILITY OR THE UNBORN CHILD,” a statement that respiratory protection and protective clothing may be required in the area, and “AUTHORIZED PERSONNEL ONLY.” Containers that can cause exposure at or above the action level, or foreseeably above the excursion limit, need precautionary labels under (j)(2)(B), and the labels stay on when containers leave the workplace.
Under §5220(j)(3)(A), employees potentially exposed at or above the action level must be trained at the time of initial assignment and at least annually. The content in (j)(3)(B) and (C) includes the requirements of the standard and where to find it, the operations where EtO is present, the medical surveillance program, detection methods, the hazards of EtO, and the protective measures in use, including the employer’s hazard communication program.
What to Do This Week
- Pull the most recent full-shift and 15-minute results and confirm the monitoring frequency matches §5220(d)(3) for each job classification.
- Identify the short tasks (door opening, cylinder change, biological indicator removal, aeration entry) and confirm each has STEL data.
- Check that the written compliance program and emergency plan were reviewed within the last 12 months under §5220(f)(2)(C).
- Match the medical surveillance roster to everyone at or above the action level for 30 or more days a year.
If your sterilization or EtO operation needs exposure monitoring, a program review or a gap check against §5220, I can help through my chemical exposure assessment and medical surveillance and recordkeeping services. Request a consultation or call (626) 546-9384.