Service area: Available in California, Nevada, Arizona, Oregon, Washington, Idaho, Montana, Utah, Wyoming, Colorado, New Mexico, North Dakota, South Dakota, Texas, Oklahoma, Louisiana, Nebraska, Alabama, Arkansas, Connecticut, Delaware, Florida, Georgia, Illinois, Indiana, Iowa, Kansas, Kentucky, Maine, Maryland, Massachusetts, Michigan, Minnesota, Mississippi, Missouri, New Hampshire, New Jersey, New York, North Carolina, Ohio, Pennsylvania, Rhode Island, South Carolina, Tennessee, Vermont, Virginia, West Virginia and Wisconsin.
A battery energy storage fire leaves two problems behind: why it happened, and what it left in the air, on the ground and on the people who responded. McNeil Safety Consulting investigates both, for owners, insurers, contractors, municipalities and the counsel representing any of them.
The scale of the risk is now on record. The Moss Landing facility fire of 16 January 2025 involved a 300 MW system of roughly 100,000 cells, about 55 percent of which EPA reported as damaged. Most failures are smaller, and most are decided in the first weeks — by what was preserved, what was sampled and who controlled the data.
How these systems fail
Thermal runaway in a single cell releases heat and flammable gas — hydrogen, carbon monoxide, hydrocarbons — along with hydrogen fluoride. Whether that stays a single-cell event or becomes a module, rack or enclosure fire depends on the design and on systems that sit outside the cells: the battery management system, the controls, thermal management, detection, ventilation and explosion control. In an enclosed container the gas can accumulate before ignition, which is why NFPA 855 requires explosion control under NFPA 68 or NFPA 69, and why the firefighter injuries at the 2019 McMicken facility in Arizona came from a deflagration when a container door was opened, not from the fire.
EPRI’s analysis of failure incidents (May 2024) found balance-of-system and controls behind 89 percent of classified root causes and integration, assembly and construction behind 46 percent. The investigation starts from that distribution, not from the assumption that a cell was defective.
The origin and cause investigation
The method is NFPA 921, the Guide for Fire and Explosion Investigations: hypotheses formed from the data and tested against it, with the scene, the physical evidence and the electronic record each checked against the others. A battery fire adds evidence a structure fire does not have.
- BMS and SCADA data — cell voltages and temperatures, alarms, contactor states and the order in which they changed. Preservation demands go out first; data logs are overwritten.
- Commissioning and maintenance records, including what California now requires under CPUC General Order 167-C — logbooks, maintenance and operation plans.
- The UL 9540A report and the hazard mitigation analysis, compared with what actually happened. A failure that propagated further than the test predicted is a central finding.
- Detection, suppression, ventilation and explosion-control performance — whether each system operated, when, and as designed.
- Fire department records — dispatch times, tactics, gas readings and the decision points of the response.
- Physical examination of modules and racks, coordinated with every interested party so that no one can later claim spoliation.
After the fire: exposure, re-entry and clearance
Responders, site workers, cleanup crews and neighbors each have an exposure question. Hydrogen fluoride drives most of them: the ACGIH TLV is a 2 ppm ceiling with a skin notation and the NIOSH REL a 6 ppm 15-minute ceiling, while the standard integrated method, NIOSH 7906, samples over a window much longer than a venting event. A clean-looking time-weighted result does not rule out a peak.
- Reconstruction of responder and worker exposure from gas readings, meteorology and the event timeline
- Re-entry criteria and air monitoring before workers return to the enclosure area
- Surface wipe sampling for fluoride and metals (nickel, cobalt, manganese, lithium) on equipment, vehicles and nearby property
- Cleanup work planned under HAZWOPER — 8 CCR §5192 and 29 CFR 1910.120 — with a site-specific health and safety plan
- Clearance sampling and a written basis for returning the area to use
Litigation and claims
BESS failures produce product liability, construction defect, subrogation, nuisance and personal injury claims, often all at once. Michael is retained as a consulting or testifying expert and prepares reports, declarations and testimony under Federal Rule of Evidence 702 and California Evidence Code §801, for plaintiffs and defendants after a conflict check.
Frequently asked questions
What should an owner do in the first 48 hours?
Keep people out until the atmosphere and the remaining modules are assessed, preserve BMS and SCADA data, photograph before anything is moved, and notify every party who may have an interest so the evidence can be examined jointly.
Can surface contamination be measured after the smoke has cleared?
Yes. Fluoride and metal residues persist on surfaces and are sampled by wipe and analyzed by an accredited laboratory. The results guide cleaning and support or refute property and exposure claims.
Do you investigate outside California?
Yes, anywhere in the lower 48 states.
Call immediately after a failure
Every investigation is handled by Michael personally and never subcontracted. Call (626) 546-9384 or request a consultation. Related work: BESS safety and compliance, chemical exposure assessment, death investigation and expert witness work.
States We Serve
McNeil Safety Consulting provides this service to clients in the following states:
- California
- Nevada
- Arizona
- Oregon
- Washington
- Idaho
- Montana
- Utah
- Wyoming
- Colorado
- New Mexico
- North Dakota
- South Dakota
- Texas
- Oklahoma
- Louisiana
- Nebraska
- Alabama
- Arkansas
- Connecticut
- Delaware
- Florida
- Georgia
- Illinois
- Indiana
- Iowa
- Kansas
- Kentucky
- Maine
- Maryland
- Massachusetts
- Michigan
- Minnesota
- Mississippi
- Missouri
- New Hampshire
- New Jersey
- New York
- North Carolina
- Ohio
- Pennsylvania
- Rhode Island
- South Carolina
- Tennessee
- Vermont
- Virginia
- West Virginia
- Wisconsin
To confirm coverage for your site, call (626) 546-9384.