Flammable Liquid Storage and Handling Under Title 8

By Michael Karl McNeil, REP, RIH, EPP, QSD

Most general industry workplaces in California keep some flammable liquid on hand: solvents for parts cleaning, thinners and coatings for maintenance, fuel for equipment, adhesives on a production line. The rules for storing and handling those liquids sit in Group 20 of the General Industry Safety Orders, and they are more specific than many written programs reflect. This post covers the sections that apply to a typical plant, shop or warehouse.

Where the Rules Are and How Liquids Are Classified

Group 20, “Flammable Liquids, Gases and Vapors,” contains the definitions in Article 134 (§5415), general vapor rules in Article 135, container and portable tank storage in Article 141 (§§5531 through 5543), and industrial plants in Article 142 (§§5545 through 5551).

Classification drives every limit. Under §5415, a flammable liquid has a flashpoint at or below 199.4°F (93°C), and is split into four categories:

  • Category 1: flashpoint below 73.4°F (23°C) and boiling point at or below 95°F (35°C).
  • Category 2: flashpoint below 73.4°F (23°C) and boiling point above 95°F (35°C).
  • Category 3: flashpoint at or above 73.4°F (23°C) and at or below 140°F (60°C).
  • Category 4: flashpoint above 140°F (60°C) and at or below 199.4°F (93°C).

A combustible liquid under §5415 has a flashpoint above 199.4°F (93°C). The same section defines a container as a vessel of 60 U.S. gallons or less, and a safety can as a listed container of not more than five gallons with a spring-closing lid and spout cover and a flame arrester. The safety data sheet for each product gives the flashpoint and boiling point you need to assign a category. In the inventories I review, the category column is often missing, which makes every other limit guesswork.

Scope of the Container Storage Article

Section 5531 applies Article 141 to flammable or combustible liquids in containers up to 60 gallons and portable tanks up to 660 gallons, including flammable aerosols. Its exceptions include fuel in the tanks of vehicles and engines, beverages in containers of one gallon or less, certain consumer items, and paints, oils, varnishes and similar mixtures used for painting or maintenance when not kept for more than 30 days. Maintenance coatings kept longer than 30 days are back inside the article.

Container Limits: Table FL-2

Under §5532(a), only approved containers and portable tanks may be used. Section 5532(c) requires them to conform to Table FL-2, which sets these maximum sizes:

  • Glass or approved plastic: 1 pint for Category 1, 1 quart for Category 2, 1 gallon for Category 3 and for Category 4 and combustible liquids.
  • Metal (other than DOT drums): 1 gallon for Category 1, 5 gallons for Categories 2, 3 and 4 and combustible liquids.
  • Safety cans: 2 gallons for Category 1, 5 gallons for the others.
  • Metal drums (DOT specification): 60 gallons for all categories.
  • Approved portable tanks: 660 gallons for all categories.

Section 5532(c) carries a narrow exception allowing glass or approved plastic containers up to 1 gallon for Category 1 or 2 liquids where metal contact would make the liquid unfit or the liquid would corrode metal, and the process quantity conditions in the exception are met.

How Much Can Sit Outside a Cabinet

For industrial plants where flammable liquids are incidental to the main business, §5545(a)(2) caps the quantity in a building outside an inside storage room or storage cabinet at:

  • 25 gallons of Category 1 flammable liquids in containers, under §5545(a)(2)(A);
  • 120 gallons of Category 2, 3 or 4 flammable liquids, or liquids with a flashpoint above 199.4°F (93°C), in containers, under §5545(a)(2)(B); and
  • one portable tank up to 660 gallons of those liquids, under §5545(a)(2)(C).

Other occupancies have their own limits. Section 5538(a) restricts office, educational and institutional occupancies to 1-gallon containers for Category 1, 2 or 3 liquids (2 gallons for safety cans), no more than 10 gallons combined outside a cabinet or room unless in safety cans, and no more than 25 gallons combined in safety cans. Section 5537 requires storage above 10 gallons of Category 1, 2 or 3 liquids combined, or 60 gallons of Category 4, in assembly occupancies, buildings with more than three dwelling units, and hotels to be in a cabinet, safety cans or a qualifying inside storage room. Warehouses follow Tables FL-4 and FL-5 under §§5540 and 5541.

Storage Cabinets: §5533

Under §5533(a), not more than 120 gallons of Category 1, 2, 3 and 4 flammable liquids may be stored in one cabinet, and of that, not more than 60 gallons may be Category 1, 2 or 3. No more than three cabinets may be located in a single fire area, except that in an industrial occupancy additional cabinets or groups of up to three may be located in the same fire area if each is separated by at least 100 feet.

Section 5533(b) sets the performance standard: internal temperature may not exceed 325°F during a ten-minute fire test, joints and seams must remain tight, and the door must stay securely closed. Cabinets must be labeled “FLAMMABLE-KEEP FIRE AWAY” in conspicuous lettering. Metal cabinets built to §5533(b)(1) are deemed compliant: No. 18 gage sheet iron, double-walled with a 1-1/2 inch air space, tight joints, a three-point door lock, and a sill raised at least 2 inches. When I inspect cabinets, I check for mixed loads that put more than 60 gallons of Category 1 through 3 inside, and for a fourth cabinet added to a fire area without the separation.

Inside Storage Rooms: §§5534 and 5535

An inside storage room is a building feature, not a closet with a sign. Section 5534(a) requires the fire-resistive rating stated in that section, a noncombustible liquid-tight sill or ramp at least 4 inches high (or a floor recessed at least 4 inches, or an open-grated trench), approved self-closing fire doors, and liquid-tight wall-to-floor joints. Table FL-3 in §5534(b) sets capacity by construction:

  • 2-hour rating, sprinklered: up to 500 square feet, 10 gallons per square foot.
  • 2-hour rating, not sprinklered: up to 500 square feet, 4 gallons per square foot.
  • 1-hour rating, sprinklered: up to 150 square feet, 5 gallons per square foot.
  • 1-hour rating, not sprinklered: up to 150 square feet, 2 gallons per square foot.

Section 5534(b)(2) requires gravity or continuous mechanical exhaust ventilation, and mechanical ventilation where Category 1 or 2 liquids, or Category 3 liquids with a flashpoint below 100°F, are dispensed in the room. Mechanical systems must provide the greater of 1 cfm per square foot of floor area (not less than 150 cfm) or six air changes per hour under §5534(b)(2)(B), with exhaust and make-up openings within 12 inches of the floor under §5534(b)(2)(A) and the exhaust controlled by a switch outside the door under §5534(b)(2)(C). Section 5535 adds one clear aisle at least three feet wide, no stacking of containers over 30 gallons of Category 1, 2 or 3 liquids, and dispensing by approved pump or self-closing faucet only.

Dispensing, Bonding and Ignition Control

In industrial plants, §5545(c) requires Category 1 or 2 liquids, and Category 3 liquids with a flashpoint below 100°F, to be kept in covered containers when not in use. Under §5545(f), Category 1 and 2 liquids may be drawn from or transferred within a building only through closed piping, from original shipping containers or safety cans, by a device drawing through the top, or by gravity through a self-closing valve or faucet, and transfer by air pressure is prohibited. Section 5545(b) requires transfer areas to be separated from other operations and provided with spill control and ventilation under §5143.

Section 5549(b) prohibits dispensing Category 1 or 2 liquids, or Category 3 liquids with a flashpoint below 100°F, into containers unless the nozzle or fill pipe and the container are electrically interconnected, by metal-to-metal contact, a bond wire, or another conductive path within the resistance limit the subsection states. A drum on a rack with a bonding clip hanging unused is a deficiency under that subsection. Section 5416(c) bars ignition sources wherever vapor may exceed 25 percent of the lower explosive limit, and §5543 requires fire extinguishers rated not less than 20-B near storage rooms and storage areas, prohibits open flames and smoking in storage areas, and keeps water-reactive materials out of the same room.

What to Do This Week

  1. Build or update an inventory that lists each flammable liquid, its §5415 category and the container type and size it is kept in.
  2. Compare every container against Table FL-2 and replace oversized glass, plastic or non-safety metal containers.
  3. Total the quantities outside cabinets and rooms in each area and check them against §5545(a)(2) or the occupancy section that applies.
  4. Check each cabinet’s load, label and count per fire area against §5533.
  5. Confirm that bonding is in place and used at every point where Category 1, 2 or low-flashpoint Category 3 liquids are dispensed.